An error occurred
Duct smoke detector
CTN: FCD-350 | Product No.: F.01U.397.735Key Specifications
| Dimensions (H x W x D) (cm) | 24.13 cm x 19.05 cm x 6.35 cm | |||
| Dimensions (H x W x D) (in) | 9.50 in x 7.50 in x 2.50 in | |||
| Weight (lb) | 3 lb | |||
| Detector head type | Convential photoelectric | |||
| Housing material | 18 G.A. steel backbox, clear plastic cover | |||
| Sampling tubes | 2.5 ft, 5 ft or 10 ft | |||
| Visual indicators | PILOT: Green - Normal | Off - Shutoff/Detector missing ALARM: Off - Normal | Yellow - Check voltage/Detector head | Red - Alarm |
| Material | Plastic (ABS) | |||
| Color (RAL) | RAL 1014 Ivory |
| Operating temperature | Inside duct: 0°C (32°F) ~ 38°C (100°F) Housing ambient: 0°C (32°F) ~ 49°C(120°F) |
| Storage temperature (°C) | -30 °C – 70 °C |
| Storage temperature (°F) | -22 °F – 158 °F |
| Ambient temperature | 0°C (32°F) - 38°C (100°F |
| Operating relative humidity, non-condensing (%) | 10% – 93% |
| Usage | Indoor/Dry |
| Air velocity | 1000 - 4000 ft/min. |
| Sensitivity | 1.36-2.33%/FT @ 4000FPM |
| Input voltage | Alarm: 24 VDC, 78 mA | 24 VAC, 370 mA | 115 AC, 48 mA | 230 VAC, 31 mA Normal standby : 24VDC 20mA | 24VAC 263mA | 115AC 15mA | 230VAC 10mA |
| Standby current | 20 mA @ 24 VDC | ||||||
| Alarm current | 78 mA @ 24 VDC |
Parts included with this product
| Quantity | Component |
|---|---|
| 1 | Detector |
| 1 | Hardware pack |
| 1 | Installation guide |